SmartGen HMC6 Power Management Controller
SmartGen HMC6 Power Management Controller
SmartGen HMC6 Power Management Controller
SmartGen HMC6 Power Management Controller
SMARTGEN

SmartGen HMC6 Power Management Controller

Regular price $2,445.00 $2,445.00
Shipping calculated at checkout.

Technical Parameters:
Display 4.3 inches TFT-LCD (480*272)
Operation Panel Silicon Rubber
Language Chinese & English
Digital Input 10
Relay Output 17
AC System 1P2W/2P3W/3P3W/3P4W
Alternator Frequency 50/60Hz
kW/Amp Detecting & Display ●
LA16 Module Extension ●
DIN16 Module Extension ●
DOUT16B Module Extension ●
Monitor Interface RS485
Programmable Interface USB/RS485
RTC & Event Log ●
AVR ●
GOV ●
DC Supply DC(8~35)V
Case Dimensions(mm) 266*182*45
Panel Cutout(mm) 214*160
Operating Temp. (-25~+70)℃
Display LCD(480*272)
Operation Panel Silicon Rubber
Language Chinese & English & Others
Alternator Frequency 50/60Hz
Monitor Interface USB/RS485
RTC & Event Log ●
DC Supply DC(8-35)V
Case Dimensions(mm) 266*182*45
Panel Cutout(mm) 214*160
Operating Temp. (-25~+70)℃

Product Overview:
The HMC6 protection and power management controller is a standard power management system for marine applications. The system carries out generator control, supervision and protection functions. The power management functions are calculated by all diesel generator units, making the system a true multi-master system. One of the diesel generator units is internally defined as the "command unit". This unit is the one where start priority and other power management-related functions are calculated.

The system can handle up to 16 diesel generators to automatic synchronization and load sharing. Should the command unit fail, the power management calculations will automatically be transferred to the next available unit. The internal communication between the units is carried out via internal CANbus. This CANbus is intended for internal communication use only and cannot be connected to other external CANbus systems.

PERFORMANCE AND CHARACTERISTICS:

1. Dynamic synchronizing: detect the phase angle difference, voltage difference and frequency difference automatically to perform synchronization as soon as possible.
2. Load sharing: Schedule the start and stop of genset and share load equally automatically.
3. Heavy consumer control: Start the additional genset automatically if the power is not enough when the function is active.
4. NEL trip: Trip some non-essential load if over power condition occurs.
5. Light load: The genset is still running if the load has fallen below the shutdown set value when the function is active.
6. Suitable for 3-phase 4-wire, 3-phase 3-wire, single phase 2-wire, and 2-phase 3-wire systems with frequency 50/60Hz;
7. Selectable start mode: Cyclic start; Linear start; Duty Time start;
8. 480x272 LCD with backlight, multilingual interface (including English, Chinese or other languages) which can be chosen at the site, making commissioning convenient for factory personnel;
9. Parameter setting: parameters can be modified and stored in internal FLASH memory and cannot be lost even in case of power outage; most of them can be adjusted using front panel of the controller and all of them can be modified using PC via USB or RS485 ports;
10. Event Log:Maximum 99 pieces of trip alarms, trip and stop alarms can be saved in chronological sequence in internal memory, which means that they will not be lost in case of power off.